File: nutdrv_siemens_sitop.8

package info (click to toggle)
nut 2.8.1-5
  • links: PTS, VCS
  • area: main
  • in suites: trixie
  • size: 18,284 kB
  • sloc: ansic: 108,785; sh: 9,370; cpp: 3,370; makefile: 2,842; python: 1,029; perl: 763; xml: 47
file content (271 lines) | stat: -rw-r--r-- 8,774 bytes parent folder | download
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
'\" t
.\"     Title: nutdrv_siemens_sitop
.\"    Author: [see the "AUTHOR" section]
.\" Generator: DocBook XSL Stylesheets vsnapshot <http://docbook.sf.net/>
.\"      Date: 10/31/2023
.\"    Manual: NUT Manual
.\"    Source: Network UPS Tools 2.8.1
.\"  Language: English
.\"
.TH "NUTDRV_SIEMENS_SITOP" "8" "10/31/2023" "Network UPS Tools 2\&.8\&.1" "NUT Manual"
.\" -----------------------------------------------------------------
.\" * Define some portability stuff
.\" -----------------------------------------------------------------
.\" ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
.\" http://bugs.debian.org/507673
.\" http://lists.gnu.org/archive/html/groff/2009-02/msg00013.html
.\" ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
.ie \n(.g .ds Aq \(aq
.el       .ds Aq '
.\" -----------------------------------------------------------------
.\" * set default formatting
.\" -----------------------------------------------------------------
.\" disable hyphenation
.nh
.\" disable justification (adjust text to left margin only)
.ad l
.\" -----------------------------------------------------------------
.\" * MAIN CONTENT STARTS HERE *
.\" -----------------------------------------------------------------
.SH "NAME"
nutdrv_siemens_sitop \- driver for the Siemens SITOP UPS500 series UPS
.SH "NOTE"
.sp
This man page only documents the hardware\-specific features of the \fBnutdrv_siemens_sitop\fR driver\&. For information about the core driver, see \fBnutupsdrv\fR(8)\&.
.SH "SUPPORTED HARDWARE"
.sp
\fBnutdrv_siemens_sitop\fR supports Siemens UPS models from the SITOP UPS500 series\&. Some models have a serial port, others have a USB port\&. The models with USB port actually contain a serial\-over\-USB chip, so as far as this driver is concerned, all models are serial models\&. This driver should work with all models in the SITOP UPS500 series, as long as your kernel has support for the serial port device (see section \fBUSB driver\fR below)\&.
.if n \{\
.sp
.\}
.RS 4
.it 1 an-trap
.nr an-no-space-flag 1
.nr an-break-flag 1
.br
.ps +1
\fBNote\fR
.ps -1
.br
.sp
This driver has only been tested with the SITOP UPS500S\-2\&.5 with USB port (Siemens product number 6EP1933\-2EC41)\&.
.sp .5v
.RE
.SH "DEVICE SETTINGS"
.sp
The UPS is configured via DIP\-switches\&. For correct functioning in combination with NUT, set the DIP\-switches to the following:
.PP
\fBswitch 1\-4\fR
.RS 4
Choose whatever suits your situation\&. Any combination will work with NUT\&.
.RE
.PP
\fBswitch 5\fR (⇒ / t)
.RS 4
Set to OFF (t)\&. This ensures that the UPS will not cut power unless NUT tells it to do so (or unless the batteries are exhausted)\&.
.RE
.PP
\fBswitch 6\-10\fR (delay)
.RS 4
Set to OFF (minimum delay)\&. Setting a higher delay will actually also work, but any command from NUT will be delayed as well before being executed by the UPS\&. With the minimum setting, it will already take 5 seconds before a command from NUT is executed\&.
.RE
.PP
\fBswitch 11\fR (INTERR\&.)
.RS 4
Set to ON (interrupt the output after the timer expires)\&. This ensures that the UPS briefly interrupts the output power in response to the shutdown\&.return command\&. See the section
\fBInstant Commands\fR
below\&.
.RE
.PP
\fBswitch 12\fR (ON/OFF)
.RS 4
set to ON (enable the UPS functionality)\&. Without this, the UPS will never supply power from its batteries\&.
.RE
.SH "USB DRIVER"
.sp
The USB\-versions of the UPS contain an FTDI USB\-to\-serial converter chip\&. It is programmed with a non\-standard product ID (for example \fI0403:e0e3\fR), but can still be used with the normal ftdi_sio driver\&.
.if n \{\
.sp
.\}
.RS 4
.it 1 an-trap
.nr an-no-space-flag 1
.nr an-break-flag 1
.br
.ps +1
\fBNote\fR
.ps -1
.br
.sp
The following hints may be specific to GNU/Linux\&.
.sp .5v
.RE
.sp
Use \fBlsusb\fR to figure out which product ID is used in your model, and replace all occurrences of \fIe0e3\fR in the following examples with the actual Product ID\&.
.sp
.if n \{\
.RS 4
.\}
.nf
modprobe ftdi_sio
echo 0403 e0e3 > /sys/bus/usb\-serial/drivers/ftdi_sio/new_id
.fi
.if n \{\
.RE
.\}
.sp
If your system uses \fBudev\fR, this can be automated via a udev rule:
.sp
.if n \{\
.RS 4
.\}
.nf
ACTION=="add", ATTRS{idVendor}=="0403", ATTRS{idProduct}=="e0e3", \e
  RUN+="/sbin/modprobe ftdi_sio", \e
  RUN+="/bin/sh \-c \*(Aqecho 0403 e0e3 > /sys/bus/usb\-serial/drivers/ftdi_sio/new_id\*(Aq"
.fi
.if n \{\
.RE
.\}
.sp
You can use the following udev rule to obtain a predictable device name, for example \fI/dev/ttyUPS\fR:
.sp
.if n \{\
.RS 4
.\}
.nf
SUBSYSTEM=="tty" ATTRS{idVendor}=="0403", ATTRS{idProduct}=="e0e3" SYMLINK+="ttyUPS"
.fi
.if n \{\
.RE
.\}
.SH "POLLING"
.sp
The UPS does not have a special \fIget status\fR command\&. Instead, it continuously sends out status update messages (tens of messages per second)\&. Every \fBpollinterval\fR, these messages are read from the serial port buffer\&.
.sp
In order to react quickly on status changes from the UPS, and to prevent the serial buffer from overflowing, \fBpollinterval\fR should be set to a relatively low value\&. The recommended value is 1 (second)\&.
.SH "EXTRA ARGUMENTS"
.sp
This driver supports the following optional settings:
.PP
\fBmax_polls_without_data\fR=\fInum\fR
.RS 4
The serial port is polled periodically for new data (see
\fBPolling\fR)\&. If there is no valid new data after
\fInum\fR
polls, it is assumed that communication with the UPS is lost\&. The default value is 2\&. Lower values may cause spurious
\fIData stale\fR
messages, especially at startup\&.
.RE
.SH "INSTANT COMMANDS"
.PP
\fBshutdown\&.return\fR
.RS 4
The behavior of this command depends on the line state:
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
\fBon line\fR: after 5 seconds (or longer, if DIP switches 6\-10 are not OFF), the UPS will shut off its output\&. After another 5 seconds, the output is activated again\&.
.RE
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
\fBon battery\fR: after 5 seconds (or longer, if DIP switches 6\-10 are not OFF), the UPS will shut off its output\&. The output will stay off, until the line voltage has returned\&.
.RE
.RE
.PP
\fBshutdown\&.stayoff\fR
.RS 4
The behavior of this command depends on the line state:
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
\fBon line\fR: after 5 seconds (or longer, if DIP switches 6\-10 are not OFF), the UPS will shut off its output\&. The output stays off, until the line voltage has been removed for at least 1 second, and has been re\-applied\&.
.RE
.sp
.RS 4
.ie n \{\
\h'-04'\(bu\h'+03'\c
.\}
.el \{\
.sp -1
.IP \(bu 2.3
.\}
\fBon battery\fR: this command behaves the same as
\fBshutdown\&.return\fR\&.
.RE
.RE
.SH "INSTALLATION"
.sp
Make sure that your operating system has created a serial device for the UPS\&. See the section \fBUSB driver\fR for more information\&.
.sp
Next, make sure that NUT has access rights to this device file\&. For example, by creating a udev rule that grants permission to the NUT user, or by adding the NUT user to a user group that can access serial devices (e\&.g\&. the \fBdialout\fR group on Debian\-based systems)\&.
.SH "DIAGNOSTICS"
.sp
You can verify the correct functioning of the hardware, by monitoring the serial port with a terminal program, for example picocom:
.sp
.if n \{\
.RS 4
.\}
.nf
picocom \-b 9600 \-d 8 \-p n /dev/ttyUPS
.fi
.if n \{\
.RE
.\}
.sp
NUT must not be running when you do this\&. You should now see a continuous stream of 5\-character texts coming in, for example:
.sp
.if n \{\
.RS 4
.\}
.nf
BUFRD
BA>85
DC_OK
.fi
.if n \{\
.RE
.\}
.sp
To exit picocom, use Ctrl\-A Ctrl\-X\&.
.SH "KNOWN ISSUES AND BUGS"
.PP
\fBUntested models\fR
.RS 4
As mentioned under
\fBSupported hardware\fR, this driver has not been tested with all models in the SITOP UPS500 series\&.
.RE
.PP
\fBData stale messages\fR
.RS 4
The firmware in these UPSes is quite buggy\&. After sending data to the UPS, it sometimes stops sending status updates\&. This driver tries to prevent this (e\&.g\&. by sending commands twice, and by sending additional LF characters after each command)\&. Once the UPS is in this state, communication can only be restored by rebooting the UPS, or by unplugging and reconnecting the USB cable\&. During normal operation, no commands are sent to the UPS at all (only at shutdown), so this issue is expected to have little impact on usability\&. It is not sure if the serial models are affected by this issue as well\&.
.RE
.SH "AUTHOR"
.sp
Matthijs H\&. ten Berge
.SH "SEE ALSO"
.SS "The core driver:"
.sp
\fBnutupsdrv\fR(8)
.SS "Internet resources:"
.sp
The NUT (Network UPS Tools) home page: https://www\&.networkupstools\&.org/